The HCRZ-II Comprehensive transformer Winding Deformation Tester employs two distinct testing methods—the Frequency Response Method and the Low-Voltage Short-Circuit Impedance Method—to measure and diagnose the windings of medium-to-large-scale transformers. By comprehensively reflecting the winding characteristics of the transformer, this product stands as the first of its kind in the nation to feature such industry-leading technology.
Product Features
Utilizes a Windows-based platform, compatible with Windows 2000, Windows XP, and Windows Vista.
The accompanying software supports remote debugging, diagnostics, maintenance, and upgrades of the device, facilitating convenient on-site technical support from the manufacturer.
Automatically calculates relevant test parameters, diagnoses the extent of winding deformation, and provides reference conclusions for the diagnosis.
Features robust software management capabilities designed with on-site operational needs in mind; it automatically saves environmental condition parameters to serve as a basis for subsequent transformer winding deformation diagnostics. Measurement data is automatically saved to disk, and a color printing function is included to facilitate the generation of test reports for users.
The software features a highly user-friendly design; most measurement conditions are presented as selectable options, minimizing the need for extensive manual data entry while on-site and thereby enhancing user convenience.
The software demonstrates a high degree of intelligence; once the input and output signals are properly connected, the entire measurement process can be completed simply by pressing a single button.
Housed in a dedicated shock-proof case, the device is protected against vibration and moisture, ensuring ease of portability and handling.
Technical Parameters
Working Principle: Integrates both the Frequency Response Method and the Impedance Method.
Signal Source: Outputs a standard sine wave signal; the output amplitude is software-adjustable, with a maximum amplitude of ±10V and an output impedance of 50Ω.
Measurement Range: The excitation channel operates on a fixed range of ±10V; the response channel features multiple selectable ranges that automatically adjust during the measurement process, accommodating a maximum input signal of ±25V. Acquisition Channel Quantization Resolution: 16-bit
Acquisition Channel Maximum Static Error: < 0.2%
Maximum Channel Storage Capacity: 128k samples
Maximum Sampling Rate per Channel: 20 MSps
Acquisition Channel Input Impedance: 1 MΩ
Frequency Sweep Measurement Range: 1 kHz – 2000 kHz
Sweep Mode: Linear or logarithmic frequency sweep distribution
Sweep Frequency Accuracy: The frequency accuracy of the sine wave output from the signal source is no greater than 0.01%
Voltage Measurement: Range 15 V – 500 V; Accuracy ±1%
Current Measurement: Range 0.25 A – 50 A; Accuracy ±1%
Impedance Measurement: Range 0 – 100%; Accuracy ±1%
Active Power: ±0.2% (0.1 < cosφ ≤ 1); ±0.5% (0.02 < cosφ ≤ 0.1)
Reactive Power: ±0.2%
Power Supply Frequency: Range 45 Hz – 65 Hz; Accuracy ±0.05%